Disconnect Switch Center Break Isolator and Double Break Isolator

Disconnector for 220kV SubstationIntroduciton;These disconnectors are , no load switching devices which physically isolate the lines. They are designed forhorizontal outdoor application and can also be designed for vertical installation. For earthing and closing ofswitchyard portions of the installation, the earthing&n

Featured Products

Disconnector for 220kV Substation
Disconnector Center Break Isolator and Double Break Isolator

Introduciton;
These disconnectors are , no load switching devices which physically isolate the lines. They are designed for
horizontal outdoor application and can also be designed for vertical installation. For earthing and closing of
switchyard portions of the installation, the earthing switches are provided on disconnector. If required.
The following documents were referred to during the preparation of this specification. In case of conflict, the
provisions of this specification shall take precedence.

IEC 129:1975: Alternating Current Disconnectors (Isolators) and Earthing Switches
IEC 60694:2002: Common Specifications for High Voltage Switchgear and Controlgear
BS 729: Hot dip galvanized coating on iron and steel articles
IEC62271-102
Isolator (Disconnector) - a mechanical switching device which provides, in the open position, an isolating
distance in accordance with Electrical Safety requirements.


SERVICE CONDITIONS
The isolator shall be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m
above sea level, humidities of up to 90%, average ambient temperature of +30ºC with a minimum of -1ºC and a
maximum of +40ºC and heavy saline conditions along the coast.


DESIGN AND CONSTRUCTION
1 The Isolator, Solid Link shall be designed and constructed in accordance with IEC 129 and IEC 60694.
2 The isolating link shall be of the vertical opening, designed for single phase manual operation. It shall be
easily removed and replaced by using a portable operating rod.

3 The isolating link shall incorporate double porcelain insulators to suit voltage requirements and mounted on
hot dipped galvanised steel under base suitable for vertical mounting.

4 The isolating link shall be arranged so that each unit is mounted independently on an angle bracket. It shall
be supplied complete with the angle bracket and accessories suitable for mounting on 'U' type steel channel.
The drawings to be submitted shall indicate all the applicable mounting positions.

5 The isolator shall be designed such that in fully open position, it shall provide adequate electrical isolation
between the contacts on each phase. It shall conform to the requirement as single point isolation for safety.

6 All steel parts shall be hot dip galvanized to BS 729. The minimum coating of galvanizing required is 80
microns.

7 The solid link shall be removable from the mounting by use of operating rod.
8 All current carrying parts of the isolator shall be made of high conductivity material.
9 The isolator shall be fitted with clamp connectors for Aluminium (ACSR) conductor of Aluminium
(ACSR)conductor of up to 18.2mm diameter.


The rating of the complete isolator shall be as follows: -
Rated voltage 36 kV
Rated frequency 50 Hz
Rated lightning impulse withstand voltage 200 kV
Rated power frequency withstand voltage, dry 95 kV
Rated normal current 400 Amps
Rated short time withstand current for 3 sec, min. 18.0 kA
Minimum creepage distance of insulators 900 mm
 
 SOLID LINKS 11KV
 
N/ODETAIL DATA
1Description Solid link assemblcomplete with link
rated at 200A and mounting bracketPIESA 002.(SeFigure 1  to Figure 12 below)
2System conditions of service
 
 
 
a) nominal Voltage (Un) r.m.s
 
 
 
 
kV
 
 
 
 
11
b) maximum system voltage (Um) r.m.sKV12
cearthing Effective & non effective
d) FrequencyHz50
3Site conditions of service
aaltitude
 
m
 
1400
b) Operating Ambient temperature°C-1 to 40
cHumidity%85
4Rating  
aNominal voltagekV11
b) Rated currentSolid link 
A
 
200
 
Cut out base
 
A
 
200
5Electrical components  
aInsulator material specification Porcelain
Dielectric strength  
Lightning  impulse withstand (1.2/50)kV95
Powefrequency wet withstand voltage r.m.skV28
6Specific creepage distancemm/kV25
7Generainformation to be provided with bid:
Drawings and brochures showing outline and general arrangement
 
 
 
 
Yes/No
 
 
 
 
Yes
 b) Detailed drawings of all items
showing criticatolerances to be provided with bid
Yes/NoYes
8Previous Type test report/certificate on
complete solid link assembly to be provided with bid
 
Yes/No
 
Yes
10Routine tests (acceptance tests on sample
Product) to be provided on delivery
Yes/NoYes
11Applicable standard PIESA 002
12Otheapplicable standards NRS 035
SABS IEC 60282-2
SABS IEC 60186
BS 137 part 2

TRI-LINKS
 
Lot 3-(a) 11kV with interrupters
 
N/ODETAIL DATA
1TYPE 11kV pre-assembled gang
operated overhead line load break switccompletwith expulsioninterrupters
2Mounting configuration Horizontal
3Mode of operation Manually operated pole
mounted linking rod and handle withlocking facilities
 a) nominal Voltage (Un) r.m.skV11
b) maximum voltage (Um) r.m.sKV12
cearthing Effective & non effective
d) FrequencyHz50
eratecurrentAmp400
f) Fault closing capacitykA12.5
4Site conditions of service
aaltitude
 
metres
 
1400
b) Operating Ambient temperature 
°C
 
-1 to +40
c) Relative humidity%85
5Electrical components  
aInsulator material specification High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials Hot dip galvanized steeto
SAN760
Dielectric strength  
Lightning  impulse withstand (1.2/50)kV95
 Powefrequency wet withstand voltage r.m.sKV28
 Short time current rating -1seckA12.5
6creepage distancemm/kV25
7Generainformation to be provided with bid:
Drawings and brochures showing
Outline and general arrangement
 
 
 
Yes/No
 
 
 
Yes
8Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/NoYes.
9Routine tests (acceptance tests on sample
 
Product) to be provided on delivery.
Yes/NoYes
10Applicable standards IEC62271
 
FURTHER REQUIREMENTS: 
Water shall not be able taccumulate on any part of the equipment nor shall anfeature introduce moisture
intancomponent.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned
with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials sucacoppeand italloys.Loacurrent shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.
All loacurrent paths shall be so designed thathe relevant parts of the switcare capable ocarrying the specified ratecurrent without exceeding the permitted temperature rise.
 
SUPPLIMENTARNOTES
 
Suppliers should give sufficient information including drawings (which must be briefcleaand to the point) on how their switch designs addresses these requirements. Further, Suppliers may offebettealternatives that are ocost benefits to customer, It istherefore imperative that schedule "B" is completed by the tenderer. Any deviations/modifications/alternatives specification must be listed in schedule "C.
 
33kV with interrupters 
 
N/ODETAIL DATA
1TYPE 33kV pre-assembled gang
operated overhead line load break switccomplete with expulsioninterrupters
2Mounting configuration Horizontal
3Mode of operation Manually operated pole
mounted linking rod and handle withlocking facilities
 a) nominal Voltage (Un) r.m.skV33
b) maximum voltage (Um) r.m.sKV36
cearthing Effective & non effective
d) FrequencyHz50
eratecurrentAmp200
f) Fault closing capacitykA12.5
4Site conditions of service
aaltitude
 
metres
 
1400
b) Operating Ambient temperature 
°C
 
-1 to +40
c) Relative humidity%85
5Electrical components  
aInsulator material specification High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials Hot dip galvanized steeto
SAN760
Dielectric strength  
Lightning  impulse withstand (1.2/50)kV170
Powefrequency wet withstand voltage r.m.sKV70
 Short time current rating -1seckA12.5
6creepage distancemm/kV25
7Generainformation to be provided with bid:  
 Drawings and brochures showing
Outline and general arrangement
 
Yes/No
 
Yes
8Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/NoYes
9Routine tests (acceptance tests on sample
 
Product) to be provided on delivery
Yes/NoYes
10Applicable standards IEC62271
 
 FURTHER REQUIREMENTS:
 
Water shall not be able taccumulate on any part of the equipment nor shall anfeature introduce moisture intancomponent.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials sucacoppeand italloys.Loacurrent shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.
All loacurrent paths shall be so designed thathe relevant parts of the switcare capable ocarrying the specified ratecurrent without exceeding the permitted temperature rise.
  
SUPPLIMENTARNOTES
 
Suppliers should give sufficient information including drawings (which must be briefcleaand to the point) on how their switch designs addresses these requirements. Further, Suppliers may offebettealternatives that are ocost benefits to custoemr.
 
11kV without interrupters
 
N/ODETAIL DATA
1TYPE 11kV pre-assembled gang
operated overhead line switcwithoutexpulsion interrupters (non-load breakswitch)
2Mounting configuration Horizontal
3Mode of operation Manually operated pole
mounted linking rod and handle withlocking facilities
 a) nominal Voltage (Un) r.m.skV11
b) maximum voltage (Um) r.m.sKV12
cearthing Effective & non effective
d) FrequencyHz50
eratecurrentAmp400
4Site conditions of service
aaltitude
 
metres
 
1400
b) Operating Ambient temperature 
°C
 
-1 to +40
c) Relative humidity%85
5Electrical components  
aInsulator material specification High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials Hot dip galvanized steeto
SAN760
Dielectric strength  
Lightning  impulse withstand (1.2/50)kV95
Powefrequency wet withstand voltage r.m.sKV28
 Short time current rating -1seckA12.5
6creepage distancemm/kV25
7Generainformation to be provided with bid:  
 Drawing and brochureshowing
Outline and general arrangement
 
Yes/No
 
Yes
8Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/NoYes
9Routine tests (acceptance tests on sample
 
Product) to be provided on delivery
Yes/NoYes
10Applicable standards IEC62271
 
 FURTHER REQUIREMENTS:
 
Water shall not be able taccumulate on any part of the equipment nor shall anfeature introduce moisture intancomponent.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials sucacoppeand italloys.Loacurrent shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.
All loacurrent paths shall be so designed thathe relevant parts of the switcare capable ocarrying the specified ratecurrent without exceeding the permitted temperature rise
 
SUPPLIMENTARNOTES
 
Suppliers should give sufficient information including drawings (which must be briefcleaand to the point) on how their switch designs addresses these requirements. Further, Suppliers may offebettealternatives that are ocost benefits to 
 
33kV without interrupters 
 
N/ODETAIL DATA
1TYPE 33kV pre-assembled gang
operated overhead line switcwithoutexpulsion interrupters (non-load breakswitch)
2Mounting configuration Horizontal
3Mode of operation Manually operated pole
mounted linking rod and handle withlocking facilities
 a) nominal Voltage (Un) r.m.skV33
b) maximum voltage (Um) r.m.sKV36
cearthing Effective & non effective
d) FrequencyHz50
eratecurrentAmp200
4Site conditions of service
aaltitude
 
metres
 
1400
b) Operating Ambient temperature 
°C
 
-1 to +40
c) Relative humidity%85
5Electrical components  
aInsulator material specification High Temperature Vulcanised
Silicon rubber
b) Cross arm and operating controls materials Hot dip galvanized steeto
SAN760
Dielectric strength  
Lightning  impulse withstand (1.2/50)kV170
Powefrequency wet withstand voltage r.m.sKV70
 Short time current rating -1seckA12.5
6creepage distancemm/kV25
7Generainformation to be provided with bid:  
 Drawing and brochureshowing
Outline and general arrangement
 
Yes/No
 
Yes
8Previous Type test report/certificate on complete
assembly to be provided with bid
Yes/NoYes
9Routine tests (acceptance tests on sample
 
Product) to be provided on delivery
Yes/NoYes
10Applicable standards IEC62271
 
FURTHER REQUIREMENTS:
 
Water shall not be able taccumulate on any part of the equipment nor shall anfeature introduce moisture intancomponent.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials suca
coppeand italloys.Loacurrent shall not be permitted to flow through ferrous components, springs, or
sp
ring-loaded mechanisms.
All loacurrent paths shall be so designed thathe relevant parts of the switcare capable ocarrying the
s
pecified ratecurrent without exceeding the permitted temperature rise. 
 
SUPPLIMENTARY NOTES

 
Suppliers should give sufficient information including drawings (which must be briefcleaand to the point)
on 
how their switch designs addresses these requirements. Further, Suppliers may offebettealternatives
that 
are ocost benefits to.

Our Services

1.

Pre sale service

a.

make technical solution

b.

send quotation, technical data sheet and drawing

c.

prepare power transmission plan, testing plan,and shipment plan

2.

In sale service

a.

supervise the manufacturing schedule totally in accordance with the plan

b.

send photos to customer during every manufacturing process(hold point)

c.

inform the customer one week before testinng.

3.

After sale service

a.

installation and commissioning, training the workers

b.

quick response within 12 hours any time

c.

provide 12 months gurantee period normally.


FAQ

1. Q:

What is your delivery time ?

A: 

Depend on the type of transformer.

2. Q:

What is your payment term?

A: 

30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it.

3. Q:

What kind of starndard you follow?

A: 

IEC, ANSI, CSA, GB, etc

4. Q:

What kind of supporting documentation you can provide normally

A: 

Quotation,outline drawing,manufacturing plan, quality control plan
testing plan, financial report, type test report(KEMA, CESI),reference list,etc

5. Q:

What is your normal wanrranty period?

A: 

12 months after transformer operation.

6. Q:

Can u do installation and commissioningin user's site?

A: 

Yes, we can send our installation team to user's country for service.

7. Q:

Do you have any experience in this kind of transformer?

A: 

Yes, we can provide reference list for check.

8. Q:

Are you manufacturer or trading company?

A: 

Manufacturer with own import & export company.


Our advantages:

Quality Assurance

--From the very beginning, VILLE ensures quality in every step to achieve the best quality.

 Experience Sharing

--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.

 Global Service

--Wherever you are, VILLE global network will support and provide you with value.

 Quick Response

--In response to your needs without delay, VILLE  knows the value of your time.

 

Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours